Dixsen
Dixsen MES-62/30 Current Transformer – 40/5A, Class 1, 2.5VA (3 Turns)
Dixsen MES-62/30 Current Transformer – 40/5A, Class 1, 2.5VA (3 Turns)
Couldn't load pickup availability
Precision Metering for 40A Circuits.
The Dixsen MES-62/30 is a specialized Solid Core Current Transformer (CT) designed for accurate monitoring of lower current loads in industrial and commercial panels.
To ensure maximum accuracy at 40 Amps, this model is engineered to operate with 3 primary turns (3T). The installer must pass the primary cable through the central window three times to achieve the correct 40/5A ratio. This design allows for high-precision measurement on smaller circuits where standard single-pass CTs might lack sensitivity.
With Class 1.0 accuracy and a 2.5VA burden, this unit is perfect for feeding data to ammeters, power factor controllers, and energy management systems.
Key Features:
- 3-Turn Installation: Requires the primary cable to be looped through the window 3 times for correct operation.
- 40A Rating: Specifically calibrated for 40A circuits using the multi-turn method.
- Solid Core Stability: Fixed core construction ensures consistent performance and magnetic efficiency.
- Standard Accuracy: Rated Class 1.0, suitable for general metering and energy cost allocation.
Technical Specifications:
| Feature | Specification |
| Model | MES-62/30 |
| Primary Current | 40 A (Requires 3 Turns) |
| Secondary Current | 5 A |
| Accuracy Class | 1.0 |
| Rated Burden | 2.5 VA |
| Primary Turns | 3T |
| Core Type | Solid Core (Window Type) |
| Frequency | 50/60 Hz |
Share